beautypg.com

Emerson SAG581126000 User Manual

Page 108

background image

SAG581126000

System Application Guide

Issue AD, November 23, 2009

Spec. No. 581126000 (Model 700

NVBA

)

Page 108 of 123

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

1.3.12 External Monitoring, Reference, and Control Signals

The MCA is connected to an “Interconnect/LVD Inhibit” circuit card. This circuit card provides
spring-clamp type terminals for connection of customer wiring, as described below.

(A) Remote Test/Equalize: All Rectifier Modules can be placed into the test/equalize mode by

applying an external ground signal. The Rectifier Modules operate in the float mode when
the signal is absent.

(B) External "System Voltage" Meter Reading: Leads can be extended from the Power

System to an external voltage source. This is the voltage source the MCA monitors for
system alarms and displays as "System Output Voltage".

(C) External Voltage Sensing: Leads can be extended from the Power System to the point at

which output voltage is to regulate, such as the battery.

(D) Emergency Shutdown and Fire Alarm Disconnect: Operation of the Rectifier Modules

can be inhibited through application of an external ground signal. Manual restart is required
(by turning AC power to the Rectifier Modules off then on, or by removing and re-inserting
the Rectifier Modules). If low voltage disconnect is furnished, the battery and system output
can be wired to also disconnect from the controlled load(s). If List RA is furnished, battery
also disconnects from the system.

(E) System Fuse Alarm Input: The system fuse alarm circuit activates when a ±18 to 60 volts

DC signal is applied this terminal.

Home