beautypg.com

Assembly (list – Emerson SAG581126000 User Manual

Page 54

background image

SAG581126000

System Application Guide

Issue AD, November 23, 2009

Spec. No. 581126000 (Model 700

NVBA

)

Page 54 of 123

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

List JA: Distribution Bus Module (Part No. 509906)
(4) +24V Fuse/Circuit Breaker System Positions and
(16) –48V Fuse/Circuit Breaker Subsystem Positions

Features

♦ Dual Voltage Distribution (+24V and -48V)
♦ 500A Maximum Total Capacity, 200A Maximum –48V Subsystem Capacity
♦ (4) Load Distribution Fuse / Circuit Breaker Mounting Positions (+24V System Voltage) (3 to 100A

TPS/TLS-Type Fuses / 1 to 250A Bullet Nose Type Circuit Breakers)

♦ (16) Load Distribution Fuse / Circuit Breaker Mounting Positions (-48V Subsystem Voltage) (3 to 100A

TPS/TLS-Type Fuses / 1 to 250A Bullet Nose Type Circuit Breakers, or accepts

GMT Load Distribution

Fuse Block Assembly Kit (P/N 514432)

”.

Restrictions

Limit one dual voltage bus (List

JA

,

JB

,

JC

,

JD

,

KA

,

LB

,

LC

) per power system.

Must be installed in Main Bay (

List 1

) only.

Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3- or 4-bus row cabinet. If a distribution bus
module is mounted directly beneath, that module must be a List

AA

,

AE

,

AK

,

AM

,

BA

,

CA

,

CF

,

EA

,

NA

,

NB

,

RA

, or

RB

. If ordering more than one (1)

List 60

, List JA must be installed in bus position A (row 1) of the

distribution cabinet.

Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the
highest capacity and working to the lowest capacity.

125A, 150A, and 200A circuit breakers occupy two mounting positions. 250A circuit breakers occupy three
mounting positions.

Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty

mounting position between it and any other overcurrent protective device.

Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.

Ordering Notes

1) Order circuit breakers as required per

Table 7

.

2) Order fuses as required per

Table 8

.

Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.

3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position

per Table

9

or

11

.

4) Order lug hardware kit,

P/N 520332

as required. Kit provides all hardware required to connect load and

ground lugs for four (4) positions of a bullet nose-type distribution assembly.

1/4-20 STUD, 48 PLACES
(CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)

GROUND

BUSBAR

LOAD RETURN
CONNECTIONS

5/8"

5/8"

+24V LOAD
CONNECTIONS
(SYSTEM)

-48V LOAD

CONNECTIONS

(SUBSYSTEM)

-48V LOADS (SUBSYSTEM)

+24V LOADS

(SYSTEM)

1/4-20 THREADED HOLE, 40 PLACES
(CUSTOMER MUST SUPPLY LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT
LENGTH: 3/4")

3/4"

-48V INPUT

(Factory Connection)

Home