Displays programmer types and allows for a change in control mode. The values for the
Programmer Type are: % Carbon, Dew Point, % O2, Millivolts, Temperature Only, Dual
Temperature, Vacuum, Probe + IR, Nitrider, Carbon + Dual Temperature, or
Cascade.
Atmosphere Instrument:
Allows for a slave instrument (or internal) to be the defined atmosphere control device. The
types of instruments are: Internal Loop 1 – Internal Loop 3, Instrument 1 – Instrument
25.
Temperature Instrument:
Allows for a slave instrument (or internal) to be the defined temperature control device. The
types of instruments are: Internal Loop 1 – Internal Loop 3, Instrument 1 –
Instrument 25.
Event Instrument:
Allows for a slave instrument (or internal) to be the defined event control device. The types of
instruments are: Internal, Instrument 1 – Instrument 25.
Quench Instrument:
Allows for slave instrument (or internal) to be the defined quench control device. The types of
instruments are: Internal Loop 1 – Internal Loop 3, Instrument 1 – Instrument 25.
End of Quench Event:
Tells the programmer which event to signal end of quench (related to which relay it is
assigned). The list of possible values is: 0 – 14.
Quench Speed Event:
Tells the programmer which event will signal the quench speed. The list of possible values is: 0
– 14.
Quench Run Event:
Tells the programmer which event will signal quench run. The list of possible values is: 0 – 14.
Date and Time:
Displays the current date and time.
Default Hold Time:
This value is the default holding time for the furnace. The range is 0 to 10000.
Deviation Alarm BO delay:
This value is the delay for the burnoff if a deviation alarm is detected. The range is 0 to
10000.
Default Wait Limits
The 9200 dual loop controller uses default wait limits in conjunction with recipe programs. The
wait limits are in place to help make sure a recipe will not continue to the next step until the
temperature, atmosphere or both are within the specified range. The wait limits are both plus