User Calibration
For complete calibration of Analog Inputs start with step #2 Zero and Span
Calibration
. Click on the “click” value next to the “User Calibration” field to start the user
calibration. The
Calibration
screen will be displayed.
Step 1. Cold Junction Calibration.
If adjusting the input by a preset amount for all temperature points please calibrate the cold
junction by entering a new value plus or minus the difference of the value indicated. Wait 120
seconds and verify with a source calibration device with the correct T/C type. In the “Calibrate
Cold Junction” section, enter the temperature of the terminals and click on the Calibrate
button. This will calibrate the cold junction value.
Note: During a normal calibration procedure,
the user should zero and span all of the inputs first and then perform a cold junction calibration,
if necessary
.
Configurator – Calibration screen
Step 2. Zero then Span Calibration.
Clicking on the Next -> button will display the second screen (Input 1 calibration) for the user
calibration. Begin here for only calibrating the inputs terminals 27-32.
Cold junction will be
completed as a final step
.
Configurator – User Calibration screen 2
In the “Zero Input 1/Range 1” section, enter the zero voltage and click on the Calibrate
button. This will calibrate the zero range.
In the “Span Input 1/Range 1” section, enter the span voltage that you are sourcing in and click
on the Calibrate button. This will calibrate the span range.
Clicking on the Next -> button will display the third screen for the user calibration. Clicking on
the <- Back button will display the previous screen.