Alternate pid setup – Super Systems PC Configurator 2 User Manual
Page 124
Super Systems Inc.
Page 124 of 201
Configurator Manual #4562 Rev D
Alternate PID Setup
Configurator – Alternate PID Setup menu option
The Alternate PID Setup menu option allows for up to 16 sets of PID values to be used on all
three loops via the programmer.
This menu option is typically used for vacuum applications with the programmer.
There is a choice of PID 1 – 16, and LP1 Set 1 – LP3 Set 3.
Prop Band (0 for On/Off):
This is the proportional band for the PID setup. The range of values is –1.0 to 999.0.
Reset:
This is the reset value. The range is 0.00 through 10.00.
Rate:
This is the rate value. The range is 0.00 through 10.00.
Integral Preset:
This is the integral preset value. The range is –100 to 100.
High Limit:
This is the high limit value. The range is –100 to 100.
Low Limit:
This is the low limit value. The range is –100 to 100.
- Bazooka Probe (10 pages)
- Gold Probe (16 pages)
- HP2000 With 9100 Controller (10 pages)
- HP15 (23 pages)
- SuperOX (14 pages)
- PGA3000 (16 pages)
- PGA3500 (26 pages)
- e-TRIM (27 pages)
- 9120 with TS (80 pages)
- MGA6000 (42 pages)
- DP2000 (17 pages)
- DPC3500 (5 pages)
- MGA6010 (54 pages)
- DPC2530 (17 pages)
- Simple Dew (18 pages)
- DPL4000 (16 pages)
- H2 Sensor (17 pages)
- Hydrogen Nitrider Analyzer (12 pages)
- PH2 (19 pages)
- AC20 Quick Start (5 pages)
- XGA Viewer (46 pages)
- AC20 RS485 Modbus (62 pages)
- AC20 (114 pages)
- 20Q Calibration Manual (9 pages)
- CAT-100 (51 pages)
- 7EK 31080 (32 pages)
- 7EK 31082 Calibration Manual (5 pages)
- 7EK 31081 (36 pages)
- 7EK 31082 (34 pages)
- 20PQ (170 pages)
- X5 Calibration Manual (1 page)
- 20Q (126 pages)
- 7SL (36 pages)
- X5 (74 pages)
- 9000 Series (15 pages)
- 3L Series (54 pages)
- 9015 Series (11 pages)
- 3 Series (92 pages)
- 9010 Series (66 pages)
- 9210 Series (65 pages)
- 9130 Series (174 pages)
- PC Configurator 2 Quick Start (15 pages)
- 9100 RPS (10 pages)
- 9125 Series (235 pages)
- 9120 RPS (11 pages)