Open TC:
This is the open TC value. Clicking on this value will toggle between up scale, down scale,
one trip point, and two trip points.
Input Offset
:
The input offset value is algebraically added to the input value to adjust the input curve on
read-out. The range is –10 to 10.
Trip Point 1 Setpoint:
This is the trip point 1 setpoint value. The range is –32768 to 32768.
Trip Point 1 Force Value:
This is the trip point 1 force value. The range is –32768 to 32768.
Trip Point 1 Direction:
This is the trip point 1 direction. The options are: input above setpoint or input below
setpoint.
Trip Point 2 Setpoint:
This is the trip point 2 setpoint value. The range is –32768 to 32768.
Trip Point 2 Force Value:
This is the trip point 2 force value. The range is –32768 to 32768.
Trip Point 2 Direction:
This is the trip point 2 direction. The options are: input above setpoint or input below
setpoint.
Analog Output setup
The 9200 Dual Loop controller has the option of two analog outputs. The outputs are ranged
for a 4 – 20 milliamp signal or a 0 – 20 milliamp signal. Each output comes with a factory
default configuration dependent on the application. Each output can be modified prior to
shipment to your facility or in the field by a supervisor.
Analog Output Terminals:
Analog output 1 – terminals 24 and 25
Analog output 2 – terminals 25 and 26