Zone Assignments
A zone assignment on the 9200 dual loop controller allows the recipe programs to change
setpoints on all slave instruments of a multi-zone furnace (up to 5 zones).
*Only used when running recipes
*Slave Instrument Setup must be configured prior to Zone Assignment setup
** Atmosphere zones link instruments to Atmosphere Setpoints
** Temperature zones link instruments to Temperature Setpoints
Configurator – Zone Assignments menu option
Assignments:
The zone assignment number, with a choice of Assignment 1 through Assignment 5.
ATM Instrument Number:
The slave instrument number assigned to an atmosphere controller, with a range of 0 to 25.
ATM Zone Number:
The zone within which the atmosphere setpoint change is desired, with a range of 0 to 5.
Default Zone Offset, atm:
This is the default zone offset for atmosphere, with a range of –100.00 to 100.00.
Temp Instrument Number:
The slave instrument number assigned to a temperature controller, with a range of 0 to 25.
Temp Zone Number: