Passcode and alarm, Ip address, Event control – Super Systems PC Configurator 2 User Manual
Page 170: Vacuum gauge setup
Super Systems Inc.
Page 170 of 201
Configurator Manual #4562 Rev D
Combo example for carbon – 4 – 12 mA Air
12 – 20 mA Gas
Offset:
This is the starting point, the Process Variable value at which you get 4 milliamps. Clicking on
this value will display an input box from which the user can select a new value. The range is –
32768 to 32767.
Range:
This is a Process Variable value between 4 and 20 milliamps. Clicking on this value will display
an input box from which the user can select a new value. The range is –32768 to 32767.
Current Selection:
Provides the option of 4-20 mA or 0-20 mA control. Clicking on this value will display an
input box with a drop-down list from which the user can select either of the two values listed
above.
Offset and Range when assigned to a control loop:
Inc -- 0 = 4mA, 100 = 20mA
Dec -- 0 = 4mA, -100 = 20mA
Example: if 4 – 20 mA = 800 mV - 1200 mV
Offset = 800 (starting point)
Range = 400
Passcode and Alarm
*** This menu option is the same as the
Passcodes and Alarm
menu option under the
Configurator-9200 Drop Down Menu
. ***
IP Address
*** This menu option is the same as the
IP Address
menu option under the
Configurator-9200
Drop Down Menu
. ***
Event Control
*** This menu option is the same as the
Event Control
menu option under the
Configurator-
9200 Drop Down Menu
. ***
Vacuum Gauge Setup
The Vacuum Gauge Setup menu option allows the users the ability to set up four different
vacuum gauges. The vacuum gauge can be selected from the lower drop-down list.