Appendix b – opcodes, Control group, Alarm group – Super Systems PC Configurator 2 User Manual
Page 176: Events group

Super Systems Inc.
Page 176 of 201
Configurator Manual #4562 Rev D
Appendix B – Opcodes
See the section
Notes About Opcodes
for any opcode-specific or general notes.
Control Group
Value Opcode
Description
Temperature Atmosphere Option
0 NO-OP
No
operation
N/A
N/A
N/A
1
BRANCH
Branch to step
True step number
False step
number N/A
2
GOSUB
Go to subroutine
N/A
N/A
Program
number
3
JUMP
Jump to program
N/A
N/A
Program
number
4
LIMIT
Time limit on wait
N/A
N/A
Time in
hours:minute
s
5
PIDLOAD
Load PID set
Loop 1 set
Loop 2 set
Loop 3 set
6 RESET
Reset values and start
program
Program number
Step number
N/A
7
SET_FACT
Set factor
N/A
CO or H Factor
Wait, Wait
Up, Wait
Down
8
SET_WAIT
Set wait limits
Temperature value
N/A
N/A
9 RUN_SLAVE
Start a recipe in a slave
instrument
Program number
Step number
Instrument
number
Alarm Group
Value Opcode
Description
Temperature
Atmosphere
Option
20 ALARM
User
Alarm
N/A
N/A
Alarm number (1 –
100)
21 DEV_AL Deviation
Alarm N/A
N/A
Off,
temperature
22 HIGH_AL
High limit alarm
Temperature value
N/A
N/A
23 HIGH_PO
High percent output
alarm
Temp PO value (-200)
N/A
N/A
24
LOW_AL
Low limit alarm
Temperature value
N/A
N/A
25 LOW_PO
Low percent output
alarm
Temp PO value (-200)
N/A
N/A
Events Group
Value Opcode
Description
Temperature
Atmosphere
Option
40
EVT IN Wait for input event
Temperature
setpoint N/A
Event number OFF/ON
(2 * # + 0 or 1)
41
EVT OUT
Event output
Temperature
setpoint N/A
Event number OFF/ON
(2 * # + 0 or 1)
42
MEVT
OUT 0
Multiple event
output 0
Temperature
setpoint
Event mask (bit
map)
Event number OFF/ON
bit map
43
MEVT
OUT 1
Multiple event
output 1
Temperature
setpoint
Event mask (bit
map)
Event number OFF/ON
bit map