Passcode and alarm – Super Systems PC Configurator 2 User Manual
Page 115
![background image](https://www.manualsdir.com/files/806369/content/doc115.png)
Super Systems Inc.
Page 115 of 201
Configurator Manual #4562 Rev D
PV 1 retrans
PV3 retrans
Loop 1 inc
Loop 3 inc
Loop 1 dec
Loop 3 dec
Loop 1 combo
Loop 3 combo
PV 2 retrans
Input 1 retrans
Loop 2 inc
Input 2 retrans
Loop 2 dec
Input 3 retrans
Loop 2 combo
Input 4 retrans
Combo example for carbon – 4 – 12 mA Air
12 – 20 mA Gas
Offset:
This is the starting point, the Process Variable value at which you get 4 milliamps. Clicking on
this value will display an input box from which the user can select a new value. The range is –
32768 to 32767.
Range:
This is a Process Variable value between 4 and 20 milliamps. Clicking on this value will display
an input box from which the user can select a new value. The range is –32768 to 32767.
Current Selection:
Provides the option of 4-20 mA or 0-20 mA control. Clicking on this value will display an
input box with a drop-down list from which the user can select either of the two values listed
above.
Offset and Range when assigned to a control loop:
Inc -- 0 = 4mA, 100 = 20mA
Dec -- 0 = 4mA, -100 = 20mA
Example: if 4 – 20 mA = 800 mV - 1200 mV
Offset = 800 (starting point)
Range = 400
Passcode and Alarm
There are four levels of menus in the 9200 Dual loop controller - Operator, Supervisor,
Administrator, and SSi Special.