Relay assignments – Super Systems PC Configurator 2 User Manual
Page 164
![background image](https://www.manualsdir.com/files/806369/content/doc164.png)
Super Systems Inc.
Page 164 of 201
Configurator Manual #4562 Rev D
Tolerance Band:
This is the tolerance band for the thermocouple. The range is –9999 to 9999.
Source 2 Offset:
This is the offset for source 2. The range is –9999 to 9999.
Source 3 Offset:
This is the offset for source 3. The range is –9999 to 9999.
Relay Assignments
Configurator – Relay Assignments menu option
The 9220 controller has the option of using eight relay outputs. All of the relays have a positive
common terminal and independent negative terminals. All of the relays are configured in a
normally closed position except relay number eight, which has both a normally closed (NC) and
a normally open (NO) terminal.
Relay Output Terminals:
Relay Output 1 – terminals 7 and 8
Relay Output 2 – terminals 7 and 9
Relay Output 3 – terminals 7 and 10
Relay Output 4 – terminals 7 and 11
Relay Output 5 – terminals 7 and 12
Relay Output 6 – terminals 7 and 13
Relay Output 7 – terminals 7 and 14
Relay Output 8 – terminals 7 and 15 NC
Relay Output 8 – terminals 7 and 16 NO
Relay Output Choices:
Loop1
fwd
Event
15
event
27
Loop1 rev
Out gas hold
event 28