Series 9205 Operations Manual Rev A
98
Millivolts + Redundant TC: Control is based off of the millivolt reading and also reads temperature. Loop 3
is another thermocouple.
%Carbon + Dual Temp: This functions similarly to %Carbon. Input 2 is the control TC. IT is not used to
calculate carbon potential with input one and to control furnace temperature. Input 3 in the third loop and
is another TC.
IMPORTANT:
If the 9205 is controlling % Carbon or Dew Point, control will be disabled if either or both of
the following are true:
•
Millivolts registered by probe are below 500 mV or above 1300 mV.
•
Temperature registered by probe is below 900°F or above 2100°F.
Temperature Mode
This allows the operator to choose either degree Fahrenheit or Celsius for the temperature. The options
are °C or °F. Pressing OK will set the choice.
Loop 1 Instrument
Internal Loop 1 (typical) Instrument 5
Instrument 12
Instrument 19
Internal Loop 2
Instrument 6
Instrument 13
Instrument 20
Internal Loop 3
Instrument 7
Instrument 14
Instrument 21
Instrument 1
Instrument 8
Instrument 15
Instrument 22
Instrument 2
Instrument 9
Instrument 16
Instrument 23
Instrument 3
Instrument 10
Instrument 17
Instrument 24
Instrument 4
Instrument 11
Instrument 18
Instrument 25
Loop 2 Instrument
Internal Loop 1
Instrument 5
Instrument 12
Instrument 19
Internal Loop 2 (typical) Instrument 6
Instrument 13
Instrument 20
Internal Loop 3
Instrument 7
Instrument 14
Instrument 21
Instrument 1
Instrument 8
Instrument 15
Instrument 22
Instrument 2
Instrument 9
Instrument 16
Instrument 23
Instrument 3
Instrument 10
Instrument 17
Instrument 24
Instrument 4
Instrument 11
Instrument 18
Instrument 25
Event Instrument
Allows for a slave instrument (or internal) to be the defined event control device. The types of instruments
are: Internal, Instrument 1 – Instrument 25. Internal is typical.
Quench Instrument
Allows for slave instrument (or internal) to be the defined quench control device. The types of instruments
are: Internal Loop 1 – Internal Loop 3, Instrument 1 – Instrument 25.
End of Quench Event
Tells the programmer which event to signal end of quench (related to which relay it is assigned). The
default event for this is Event 7, but it can be changed in the furnace setup menu. This event turns on for
one (1) minute when the quench timer is complete. The list of possible values is: 0 – 14.