Temp Zone Number
This option will allow the user to set the zone number for the assignment. The range is 0 – 5.
Temp Zone Offset
This option will allow the user to enter an offset for the assignment. The range is -4000 – 4000.
Furnace Setup
The Furnace Setup menu option is an administrative
access only option. Do not make any adjustments on
the screen without first contacting Super Systems, Inc.
at (513) 772-0060.
Note for controllers with Cascade
control: When in cascade mode, the 9xxx treats loop 2
as the furnace loop and loop 3 as the load loop. It feeds
the output of the load loop into the set point of the
furnace loop
.
PVT Type
There are nine PVT choices for the 9205:
%Carbon
Cascade
Dew Point
% Carbon + Redundant TC
Millivolts
Dew Point + Redundant TC
Multi-loop
Millivolts + Redundant TC
% Carbon + Dual Temp
%Carbon: Process variable will calculate for carbon
potential along with a temperature loop. Loop 1 is
based off of Input 1 (terminals 31, 32 probe sensor
millivolts) and Input 2 (terminals 29, 30 probe TC).
These two inputs together constitute loop 1. Loop 2
comes from Input 3 (terminals 27, 28) which is
temperature control.
Cascade: Three loops of temperature control work together in a cascade setting.
Dew Point: Control will be for dew point along with a temperature loop. Loop 1 is based off of Input 1
(terminals 31, 32 probe sensor millivolts) and Input 2 (terminals 29, 30 probe TC). These two inputs
together constitute loop 1. Loop 2 comes from Input 3 (terminals 27, 28) which is temperature control.
%Carbon + Redundant TC: This functions the same way as the %Carbon option with an additional
thermocouple for Loop 3. The two thermocouples are used to control carbon, and the operator can choose
the setting that will be used.
Millivolts: Control is based on what the millivolt reading is and also reads temperature.
Dew Point + Redundant TC: This functions the same way as the Dew Point option with an additional
thermocouple for Loop 3. The two thermocouples are used to control dew point, and the operator can
choose the setting that will be used.
Multiloop: Three loops of control can be assigned as selected.