Super Systems 9205 Series User Manual
Page 191

Series 9205 Operations Manual Rev A
190
Field
Factory Default Value
Temp Wait Limit
0
Atm Wait Limit
0.00
Furnace Name
Alarm 1 Setup
Setpoint
10
Alarm Type
PV1 NC/in band
Hysteresis
1
Smart Alarm
disabled
ON Delay Time (sec)
0
0 SP blocks alarm
no
BO/Impedance inhibits alarm
no
Inhibit source
none
Disable on open input
no
Alarm 2 Setup
Setpoint
15
Alarm Type
PV2 NC/in band
Hysteresis
1
Smart Alarm
disabled
ON Delay Time (sec)
0
0 SP blocks alarm
no
BO/Impedance inhibits alarm
no
Inhibit source
none
Disable on open input
no
Alarm 3 Setup
Setpoint
1400
Alarm Type
IN3 proc high
Hysteresis
1
Smart Alarm
disabled
ON Delay Time (sec)
0
0 SP blocks alarm
no
BO/Impedance inhibits alarm
no
Inhibit source
none
Disable on open input
yes
NOTE: The default setting for the process alarm is 1400°F. By default, this alarm is triggered by input 3
unless the 9205 is controlling % Carbon with a dual thermocouple setup, in which case the alarm is
triggered by input 2.
Relay Assignments
Relay 1
loop 2 fwd
Relay 2
loop 1 fwd
Relay 3
loop 1 rev
Relay 4
burn off
Relay 5
alarm 1
Relay 6
alarm 2
Relay 7
event 0