Ssi analog input setup, Nalog, Nput – Super Systems 9205 Series User Manual
Page 118: Etup

Series 9205 Operations Manual Rev A
117
SSi Analog Input Setup
The SSi Analog Input Setup menu option allows the user an
input selection of three inputs per module, and three input
corrections per module. There are eight modules
available. It is configurable for voltage of T/C (universal
input), and it is typically used for Load T/Cs and Auxiliary
Flow Meters. Before connecting your input source to the
terminals, please verify that the input type is set up
correctly. If the Input Type is not correct, do not connect
the input source to the terminals, as damage can occur.
Please consult SSi by calling (513) 772-0060 before making
any changes.
Input Type 0 – Input Type 2
This will select the input type for the module. The options are:
B
NNM
160 mV
C
R
80 mV
E
S
40 mV
J
T
20 mV
25.6 volts**
K
2.56 volts
4-20 mA/124
Ω
12.8 volts**
N
1.28 volts
4-20 mA/62
Ω
** - When the specified input type is selected, a jumper located inside the case will need
to be placed on that specific input for reading this selection. If jumper is not placed on
input, then damage could occur to the board.
Input 0 Correction – Input 2 Correction
This option will set a correction curve for the input. The options for the input corrections are: not used,
Curve 1 – Curve 3.
Input 1 Open T/C – Input 3 Open T/C
This option will allow the user to set the direction of the open T/C for each input. The options are: Up Scale
or Down Scale.