Appendix d – 9205 instrument alarms – Super Systems 9205 Series User Manual
Page 182

xSeries 9205 Operations Manual Rev A
181
Appendix D – 9205 Instrument Alarms
This appendix provides a list of alarms programmed into the 9205 controller. The table below provides the alarm name, alarm text (as presented
in Configurator), the condition(s) under which the alarm is generated, and information on user-accessible settings that affect the triggering of the
alarm.
Alarm Description
Register/Bit Location
Type
Values
Alarm Condition(s)
Applicable User-
Configurable Setting(s)
Programmer (any) alarm
141/0
Programmer
Alarm 1
141/1
Main
Alarm 2
141/2
Main
Alarm 3
141/3
Main
TC redundancy alarm
141/7
Internal System Error
141/8
Analog input CPU is no
longer responding to the
9205's main CPU.
TC Check 1->2 out of band
141/9
TC Check 1->3 out of band
141/10
TC Check 2->3 out of band
141/11
End of Quench
141/12
Programmer 2 (any) alarm
141/14
Slave coms (any) alarm
141/15
TC rise too great
163/0
Burnoff
mV insufficient drop
163/1
Burnoff
slow recovery
163/2
Burnoff
impedance too high
163/3
Burnoff
PLC Alarms (custom)
2980 - 2989
PLC
user alarm
25024/0
Programmer
deviation, atmosphere
25024/1
Programmer
high atmosphere
25024/2
Programmer
low atmosphere
25024/3
Programmer
deviation, temperature
25024/4
Programmer
high temperature
25024/5
Programmer
low temperature
25024/6
Programmer
high atm % output
25024/7
Programmer
low atm % output
25024/8
Programmer
high temperature %
output
25024/9
Programmer
low temperature % output 25024/10
Programmer