The Event ON/OFF Bitmap field will set the final condition of the events in the event mask. The opcode will
ignore the bits not in the mask and either set or reset the bits depending upon their states in the bitmap.
The options are: 0 – 15.
MEVT_OUT_1
Temperature Setpoint
Event Mask
Event ON/OFF Bitmap
This opcode will set multiple output events 16 through 31.
The Temperature Setpoint is an optional setpoint to send down. The range is -301 (disable) – 30000.
The Event Mask is the events to enable, which is the events affected. The options are: 0 – 15.
Note – Even
though the events listed are 0 – 15, they correspond to 16 – 31
.
The Event ON/OFF Bitmap field will set the final condition of the events in the event mask. The opcode will
ignore the bits not in the mask and either set or reset the bits depending upon their states in the bitmap.
The options are: 0 – 15.
Note – Even though the events listed are 0 – 15, they correspond to 16 – 31
.
MEVT_OUT_2
Temperature Setpoint
Event Mask
Event ON/OFF Bitmap
This opcode will set multiple output events 32 through 47.
The Temperature Setpoint is an optional setpoint to send down. The range is -301 (disable) – 30000.
The Event Mask is the events to enable, which is the events affected. The options are: 0 – 15.
Note – Even
though the events listed are 0 – 15, they correspond to 32 – 47
.
The Event ON/OFF Bitmap field will set the final condition of the events in the event mask. The opcode will
ignore the bits not in the mask and either set or reset the bits depending upon their states in the bitmap.
The options are: 0 – 15.
Note – Even though the events listed are 0 – 15, they correspond to 32 – 47
.
MV_INQ
N/A
Millivolt Level
Option
The millivolt inquiry is used to wait for the probe millivolts to reach the value specified in the atmosphere
data. The range is -1 to 9999.
The
LIMIT
opcode immediately following this opcode sets a time limit on the wait.
A
BRANCH
opcode immediately following this opcode can be used to change the program flow based on the
inquiry results.
NO-OP
N/A
N/A
N/A
This is a no operation code, and it does nothing. It is used as a place holder on programs that are less than
24 steps.
PIDLOAD
Loop 2
Loop 1
Loop 3
This opcode will load an alternate PID set from the controller memory.
The Loop 1 field is the alternate PID loop to use for loop 1. A value of 0 will disable the loop PID. The range
is 0 – 16.
The Loop 2 field is the alternate PID loop to use for loop 2. A value of 0 will disable the loop PID. The range
is 0 – 16.
The Loop 3 field is the alternate PID loop to use for loop 3. A value of 0 will disable the loop PID. The range
is 0 – 16.
The alternate PID loops can be set up on the
Alternate PID Setup
screen. See the
Alternate PID Setup
section for more information.