Series 9205 Operations Manual Rev A
179
Appendix C – Setup for Carbon / Dual Temperature for Quench Control
SSi’s 9205 controller is capable of controlling %Carbon and Dual Temperature loops for the purpose of
quench tank control. This guide describes how to use SSi’s Configurator to set up the 9205 controller for
%Carbon and Dual Temperature control.
Procedure
1.
Make sure that two (2) relay outputs are available. Configure the relay outputs for Alarm 1 and
Alarm 2 under Relay Assignments. See Relay Assignments.
Configuring two relay outputs for Alarm 1 and Alarm 2 relay assignments