Aux setpoint configuration, Tc extension correction curves, Etpoint – Super Systems 9205 Series User Manual
Page 124: Onfiguration, Xtension, Orrection, Urves
Series 9205 Operations Manual Rev A
123
Aux Setpoint Configuration
See the menu option Slave Instrument Setup for configuration prior to using Aux Setpoint Configuration.
Aux Set Point Configuration is an automatic set point retransmission with a corresponding custom offset
and delay to one or more of the first 3 configured slave instruments. The delay is in minutes and is only
active when the set point is dropped. This feature would most commonly be used to keep the alarm set
point of an overtemp tracking the furnace's main set point (with offset). The delay allows the furnace time
to cool below the level specified so that there is no overtemp alarm when the furnace is cooling.
Retrans to Slave 1 – Retrans to Slave 3
This option will determine which control loop to
use as the retransmission value.
The options are:
Off
Loop 1
Note – If the setpoint is 0, then the retransmission
is blocked
.
Setpoint Offset Sl 1 – Setpoint Offset Sl 3
Values entered will take the decimal point of the
PV into account, but each value is entered in whole
numbers:
Carbon: 1 = 0.01
Temperature: 1 = 1
This option will apply the offset when retransmitting the value from the control loop. The range is –32768 to
32767.
Setpoint Delay Sl 1 – Setpoint Delay Sl 3
This is measured in seconds. This option will set the number of seconds to delay before retransmitting the
value from the control loop. The range is –32768 to 32767.
TC Extension Correction Curves
This menu option will allow the user to set up to three TC
correction curves for the 9205 controller. Clicking on the
“click” value for a curve will display the curve edit form.
Note: If the first “Temperature” value and the first “Error”
value are both zero, then the curve will not be set
. The
user can enter up to ten “Temperature”/“Error”
combinations. The range for the “Temperature” field is –
300 to 9999. The range for the “Error” field is –30.000 to
30.000.