Event control, Vent, Ontrol – Super Systems 9205 Series User Manual
Page 115

Series 9205 Operations Manual Rev A
114
Delay Time
This is the time in seconds that will pass once the TCs go out of band before an alarm is activated to prevent
excessive, unnecessary alarming. The range is 0 to 3200 seconds.
TC Selection
To change this option from TC 1, the Select Mode must be in manual.
Select Mode
This allows the operator to choose whether the highest or lowest TC will automatically be chosen, or
whether it will be manually chosen by the operator. The options are highest, lowest, and manual.
NOTE: If the 9205 has redundant TC active, then digital inputs 2 and 3 can manually override the system and
force the selected TC to be TC 1 if input 1 is active or TC 2 if TC 2 is active. If both input 1 and input 2 are
active, input 1 will take precedence and make TC 1 active.
Event Control
The Event control provides the user manual
control of actual event outputs. This is useful
when testing wiring and field devices.
Programmer 1 and Programmer 2 event
outputs can be controlled. The Programmer
number is selected with the Programmer
drop-down box under the menu box in
Configurator.
Hold Instrument Number
Clicking on this value will display an input box
from which the user can select a new value.
The range is 0 to 25.
Hold Minimum PV
Clicking on this value will display an input box
from which the user can select a new value.
The range is 0 to 4000.
Hold Maximum PV
Clicking on this value will display an input box
from which the user can select a new value.
The range is 0 to 4000.
Event for Program Run
Clicking on this value will display an input box from which the user can select a new value. The range is -0
to 15. A value of -1 will disable this option.
Event for Program Reset
Clicking on this value will display an input box from which the user can select a new value. The range is -0
to 15. A value of -1 will disable this option.
Input Event 0 – Input Event 15
The input box for these events has two drop-down lists. The top list contains active and inactive, and the
bottom list contains closed and open.