Series 9205 Operations Manual Rev A
41
Zone Assignments
WARNING: This screen should not be changed
without consulting SSi at (513) 772-0060.
*Slave Instrument Setup must be configured prior to
Zone Assignment setup
The zone assignment feature allows the Series 9205
program to change set points on all instruments of a
multi-zone furnace. The Series 9205 has up to five
temperature and atmosphere zone assignments
available (Zone Assignment 1 – Zone Assignment 5).
Typically, the first zone is configured to the
programmer’s atmosphere or temperature
instrument. That is the master set point that will be propagated to the other configured zone instrument
set points on set point change. For example, the user may want to set 4 temperature zones from a recipe
where the programmer temperature instrument is loop 2. In this case, zone 1 would be configured as loop
2. Subsequent zones would be configured as previously configured slave temperature controllers.
If the
ZONE_OFF
(Zone Offset) opcode had been used in the program, the set point sent to the specified
zone instrument would have the offset added. For example, a 3-zone pit furnace, where the bottom zone
usually has a higher set point. The middle zone and the top zone usually have a lower set point. The bottom
zone temperature controller is assigned to zone 1, the middle temperature controllers to zone 2, and the
top zone controller to zone 3.
If the first three steps of a program are as shown below, then the bottom zone set point is 1775, the middle
zone is 1750, and the top zone is 1800.
Step
Opcode
Temperature
Option
1
ZONE_OFF
25
Zone 1
2
ZONE_OFF
50
Zone 3
3
SETPT
1750
The first step sets the offset for zone 1 to 25 degrees; therefore, the bottom zone controller would be sent a
set point of 1775 when step 3 is executed. Likewise step 2 sets the offset for zone 3 to 50 degrees. The top
zone then receives a set point of 1800. The middle zone controller would receive the 1750. The temperature
controller displayed on the Status Display is instrument #2. If instrument #2 were the top zone controller
then the Status Display would show the 1800-degree set point.
When using the multi-zone offset feature, the temperature controller assigned as instruments 1 and 2
should be in zones that will not be offset.
Atm Source
This will allow the user to set the atmosphere instrument for the zone assignment. The options are
Loop 1
Instrument 5
Instrument 12
Instrument 19
Loop 2
Instrument 6
Instrument 13
Instrument 20
Loop 3
Instrument 7
Instrument 14
Instrument 21
Instrument 1
Instrument 8
Instrument 15
Instrument 22
Instrument 2
Instrument 9
Instrument 16
Instrument 23
Instrument 3
Instrument 10
Instrument 17
Instrument 24
Instrument 4
Instrument 11
Instrument 18
Instrument 25