Super Systems AC20 User Manual
Page 95

93
Band alarm
Band alarm
Band alarm
Band alarm
Band alarm
Operative mode
Operative mode
Operative mode
Operative mode
Operative mode: Inside or outside programmable.
Threshold
Threshold
Threshold
Threshold
Threshold: two thresholds programmable:
- Low - from 0 to -1000 digits.
- High - from 0 to +1000 digits.
Hysteresis
Hysteresis
Hysteresis
Hysteresis
Hysteresis: programmable in engineering units from 1 to 200
digits.
Deviation alarm
Deviation alarm
Deviation alarm
Deviation alarm
Deviation alarm
Operative mode
Operative mode
Operative mode
Operative mode
Operative mode: high or low programmable.
Threshold
Threshold
Threshold
Threshold
Threshold: programmable from - 1000 to +1000 digits.
Hysteresis
Hysteresis
Hysteresis
Hysteresis
Hysteresis: programmable in engineering units from 1 to 200
digits.
SERIAL INTERFACE
SERIAL INTERFACE
SERIAL INTERFACE
SERIAL INTERFACE
SERIAL INTERFACE
Types:
Types:
Types:
Types:
Types: Optoisolated RS 485
Protocol type
Protocol type
Protocol type
Protocol type
Protocol type: MODBUS, JBUS (RTU mode).
Baud rate
Baud rate
Baud rate
Baud rate
Baud rate: programmable from 600 to 19200 BAUD.
Byte format
Byte format
Byte format
Byte format
Byte format: 8 bit.
Parity
Parity
Parity
Parity
Parity: even, odd or none programmable.
Stop bit
Stop bit
Stop bit
Stop bit
Stop bit: one.
Address
Address
Address
Address
Address: from 1 to 255.
Output voltage levels
Output voltage levels
Output voltage levels
Output voltage levels
Output voltage levels: according to EIA standard.
NOTE
NOTE
NOTE
NOTE
NOTE: The EIA standard establishes that by RS-485 interface it
is possible to connect up to 30 devices with one remote master
unit.
The serial interface of these instruments is based on “High input
impedance” transceivers; this solution allows you to connect up
to 127 devices (based on the same transceiver type) with one
remote master unit.