beautypg.com

Super Systems AC20 User Manual

Page 26

background image

24

2) During configuration parameters modify mode, the upper

display shows the selected parameter group, the lower display
shows the mnemonic code of the selected parameter while
the central display shows the value or status assigned to the
selected parameter.

3) For an easy consultation of this manual, a sheet named

"Reference parameter guide" with all the parameter
visualizations is enclosed.
The groups of configuration parameters are identified by the
"C" letter followed by A, B etc.
The "code" formed by the group and the row (i.e. C.D01
where "C.D" is configuration group1 and "01" is the row 1) is
reported, in the user manual, before each parameter
description and allows you to quickly find out the respective
parameter.

CONFIGURATION GROUP 1 [C.Dxx]

CONFIGURATION GROUP 1 [C.Dxx]

CONFIGURATION GROUP 1 [C.Dxx]

CONFIGURATION GROUP 1 [C.Dxx]

CONFIGURATION GROUP 1 [C.Dxx]
INPUT CONFIGURATION

Push the FUNC push-button

C.D01- Line frequency

C.D01- Line frequency

C.D01- Line frequency

C.D01- Line frequency

C.D01- Line frequency
Upper display: CnF.1
Lower display: Ln.Fr
Range: 50 Hz

60 Hz

C.D02- Controlled variable selection

C.D02- Controlled variable selection

C.D02- Controlled variable selection

C.D02- Controlled variable selection

C.D02- Controlled variable selection
Upper display: CnF.1
Lower display: PV.SL
Ranges:
CP = Carbon potential (span limits within 0.00% to 2.00%).
dP = Dew point (span limits within -100 to 100 °F or -75 to 40°C).
ñV = Sensor output in mV (span limits within 0 to 1500 mV).

O2 = Oxygen value as primary control variable
( The span limits are 0.0 to 25.0)