R.F10 -

R.F10 -

R.F10 -

R.F10 -

R.F10 - Alarm 3 configuration

Alarm 3 configuration

Alarm 3 configuration

Alarm 3 configuration

Alarm 3 configuration

This parameter is available only when OUT 3 is configured as
alarm 3 output (“O3.Fn” [C.E03] = “ALr.3”).
Upper display: Gr.6
Lower display: A3.Cn
Range: H.A.

= High alarm (outside band) with automatic reset.

L.A.

= Low alarm (inside band) with automatic reset.

H.A.Ac= High alarm (outside band) with automatic reset

and acknowledge.

L.A.Ac= Low alarm (inside band) with automatic reset

and acknowledge.

H.L.

= High alarm (outside band) with manual reset.

L.L.

= Low alarm (inside band) with manual reset.

NOTE

NOTE

NOTE

NOTE

NOTE: When alarm configuration has been changed, the alarm
status will be cleared.

R.F11 -

R.F11 -

R.F11 -

R.F11 -

R.F11 - Alarm 3 action

Alarm 3 action

Alarm 3 action

Alarm 3 action

Alarm 3 action

This parameter is available only when OUT 3 is configured as
alarm 3 output (“O3.Fn” [C.E03] = “ALr.3”).
Upper display: Gr.6
Lower display: A3.Ac
Range: dir

= direct action (Relay energized or SSr=1 in alarm

condition).

rEV

= Reverse action (Relay energized or SSr=1 in non

alarm condition).

R.F12 -

R.F12 -

R.F12 -

R.F12 -

R.F12 -Alarm 3 standby (mask) function

Alarm 3 standby (mask) function

Alarm 3 standby (mask) function

Alarm 3 standby (mask) function

Alarm 3 standby (mask) function

This parameter is available only when OUT 3 is configured as
alarm 3 output (“O3.Fn” [C.E03] = “ALr.3”)
Upper display: Gr.6
Lower display: A3.St
Range: OFF = Stand-by function disabled

On

= Stand-by function enabled

NOTES

NOTES

NOTES

NOTES

NOTES:
1) If the alarm is programmed as band or deviation alarm, this

function masks the alarm condition after a set point change or
at the instrument start-up until process variable reaches the
alarm threshold plus or minus hysteresis. If the alarm is
programmed as a process alarm, this function masks the alarm
condition at instrument start-up until process variable reaches
the alarm threshold plus or minus hysteresis.

2) The change from On to OFF has immediate effect, while the

change from OFF to On has effect at the next start up or set
point change