Super Systems AC20 User Manual
Page 33

31
General note on configuration group 2
General note on configuration group 2
General note on configuration group 2
General note on configuration group 2
General note on configuration group 2
Exiting from the configuration group 2 the instrument automati-
cally verifies the congruence of all parameters.
If a wrong setting is detected, the device will show:
The parameter group 2 passes the congruence test when:
1) No one of the 5 outputs is configured as control output.
2) Only one of the 5 outputs is configured as main output (“ñAin”).
3) Only one of the 5 outputs is configured as secondary output
(“SECn”).
4) If only one control output is configured, it should be the main
control output (“ñAin”).
When changing menu, the following actions are performed:
1) The "CnF.4 - Añ.UL" [C.G04] parameter will be forced to "buñ"
if its value is less than zero and only one control output has
been configured.
2) The "Gr.4 - IP" [R.D05] parameter will be forced to 50.0 if only
one control output has been configured and its value is < 0.
CONFIGURATION GROUP 3 [C.Fxx]
CONFIGURATION GROUP 3 [C.Fxx]
CONFIGURATION GROUP 3 [C.Fxx]
CONFIGURATION GROUP 3 [C.Fxx]
CONFIGURATION GROUP 3 [C.Fxx]
CONTROL OUTPUT CONFIGURATION
C.F01 - Main control output conditioning
C.F01 - Main control output conditioning
C.F01 - Main control output conditioning
C.F01 - Main control output conditioning
C.F01 - Main control output conditioning
This parameter is available only when main control output is
configured.
Upper display: CnF.3
Lower display: ñC.Cn
Range: norñ = The control output is as calculated by the PID.
CñPL = The control output is complemented (100-PID
calculated value).
C.F02 - Main control output in engineering unit
C.F02 - Main control output in engineering unit
C.F02 - Main control output in engineering unit
C.F02 - Main control output in engineering unit
C.F02 - Main control output in engineering unit
This parameter is available only when main control output is
configured.
Upper display: CnF.3
Lower display: ñ.SCL
Range: nO
= Scalable is not required
YES
= Scalable is required