By or push-button it is possible to select between:

= (monitor) this selection allows you to monitor but

not to modify the value assigned to the
configuration parameters.

=

(modify) this selection allows you to monitor and to
modify the value assigned to the configuration
parameters.

NOTES

NOTES

NOTES

NOTES

NOTES:
1) During monitor mode, the instrument continues to operate as

in run time mode.

2) When modify mode is started, the instrument stops the control

and:
- sets to OFF the control outputs;
- turns to OFF the bargraph displays;
- sets analog retransmissions to the retransmitted initial scale

value;

- sets to OFF the alarms;
- disables the serial link;
- the time out will be disabled.

3) When the modify mode is disabled by V101 (V101.3), the or

push-button pressure has no effect.

MONITOR MODE

MONITOR MODE

MONITOR MODE

MONITOR MODE

MONITOR MODE
During the run time mode, it is possible to monitor but not modify
all configuration parameters.
When it is desired to verify the instrument configuration, proceed
as follows:

1) By or push-button select the monitor mode.
2) Push the MENU push-button the display will show:

it shows that configuration group 1 is selected and it
encompasses all the input parameters.

The configuration parameter "Monitor mode" follows the "Modify
mode" sequence.

NOTES

NOTES

NOTES

NOTES

NOTES:
1) During monitor mode, the instrument continues to operate as

in run time mode.

2) During monitor mode, if no push-button is depressed for more

than 10 s (or 30 s according to "CnF.6 - t.out" [C.I08]
parameter setting), the instrument returns automatically to the
normal display mode.