CONFIGURATION GROUP 4 [C.Gxx]

CONFIGURATION GROUP 4 [C.Gxx]

CONFIGURATION GROUP 4 [C.Gxx]

CONFIGURATION GROUP 4 [C.Gxx]

CONFIGURATION GROUP 4 [C.Gxx]
AUXILIARY CONTROL PARAMETER CONFIGURATION

C.G01 - Smart function

C.G01 - Smart function

C.G01 - Smart function

C.G01 - Smart function

C.G01 - Smart function
This parameter is available only when at least one control output
is configured
Upper display: CnF.4
Lower display: Sñ.Fn
Range: dIS

= Smart function disabled

Enb

= Smart function may be enabled

C.G02 - Control action type

C.G02 - Control action type

C.G02 - Control action type

C.G02 - Control action type

C.G02 - Control action type
This parameter will be available only when at least one control
output is configured.
Upper display: CnF.4
Lower display: Cn.tP
Range: Pid

= The process is controlled by PID actions

Pi

= The process is controlled by PI actions

C.F12 -

C.F12 -

C.F12 -

C.F12 -

C.F12 -Secondary control output auxiliary condition-

Secondary control output auxiliary condition-

Secondary control output auxiliary condition-

Secondary control output auxiliary condition-

Secondary control output auxiliary condition-

i n g

i n g

i n g

i n g

i n g
This parameter will be available only when secondary control
output is configured and “SC.Cn” ("Secondary control output
conditioning" [C.F07]) is different from “norñ”.
Upper display: CnF.3
Lower display: SC.A.C
Range: bEFr = The functions listed at Note (B) are calculated

before

before

before

before

before to apply the action selected by “SC.Cn”
("Secondary control output conditioning" [C.F07])
parameter.

AFtr

= The functions listed at Note (B) are calculated

after

after

after

after

after to apply the action selected by “SC.Cn”
(“Secondary control output conditioning” [C.F07])
parameter.

Note (B)

Note (B)

Note (B)

Note (B)

Note (B)
- "Secondary control output limiters" - for more details see

[r.E06] and [r.E07] parameters.

- "Secondary control output max rate of rise" (see [r.E08]).
- "Control output display value" - for more details see "Display

function" paragraph at pag. 43 and [C.F08], [C.F09], [C.F10],
[C.F11] parameters.

- The control output value displayed by bargraph.