The Burn off sequence is the following:
- The Burn off output (OUT 4)will be turned ON for a programma-
ble period (by "Gr. 8 - "t.bOF" [R.H01] parameter).
- At the end of this period, OUT 4 will be turned OFF and the
Purge output (OUT 5) will be turned ON for a programmable
period (by "Gr. 8 - "t.PrG" [R.H02] parameter).
- At the end of this period, OUT 5 will be turned OFF, the
procedure is completed and the normal control is resumed.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
a)During the Burnoff and Purge procedures the control output,
the Adaptive algorithm and alarm status are frozen.
b)During the Burnoff and Purge procedures the input span 0 to
1500mV will be enabled, independently of the primary
controlled variable selected.
c)If a power down occurs, the current Burn off status and timings
will be lost (if automatic burn off was set, the timer will start
again from the value set by the "bF.tr" [R.H03] parameter).