1) If the alarm is programmed as band or deviation alarm, this
function masks the alarm condition after a set point change or
at the instrument start-up until process variable reaches the
alarm threshold plus or minus hysteresis. If the alarm is
programmed as a process alarm, this function masks the alarm
condition at instrument start-up until process variable reaches
the alarm threshold plus or minus hysteresis.
2) The change from On to OFF has immediate effect, while the
change from OFF to On has effect at the next start up or set
point change
R.F09 -
R.F09 -
R.F09 -
R.F09 -
R.F09 -Alarm 3 type
Alarm 3 type
Alarm 3 type
Alarm 3 type
Alarm 3 type
This parameter is available only when OUT 3 is configured as
alarm 3 output (“O3.Fn” [C.E03] = “ALr.3”)
Upper display: Gr.6
Lower display: A3.tP
Range: Proc = Alarm on process variable
bAnd = Band alarm on process variable
dEV
= Deviation alarm on process variable
NOTE
NOTE
NOTE
NOTE
NOTE: When alarm type has been changed the alarm threshold
will be forced to its default value and alarm status will be
cleared.
H.L.
= High alarm (outside band) with manual reset.
L.L.
= Low alarm (inside band) with manual reset.
NOTE
NOTE
NOTE
NOTE
NOTE: When alarm configuration has been changed, the alarm
status will be cleared.
R.F07 -
R.F07 -
R.F07 -
R.F07 -
R.F07 -Alarm 2 action
Alarm 2 action
Alarm 2 action
Alarm 2 action
Alarm 2 action
This parameter is available only when OUT 2 is configured as
alarm 2 output (“O2.Fn” [C.E02] = “ALr.2”)
Upper display: Gr.6
Lower display: A2.Ac
Range: dir
= direct action (Relay energized or SSr=1 in alarm
condition)
rEV
= Reverse action (Relay energized or SSr=1 in non
alarm condition)
R.F08 -
R.F08 -
R.F08 -
R.F08 -
R.F08 -Alarm 2 stand by (mask) function
Alarm 2 stand by (mask) function
Alarm 2 stand by (mask) function
Alarm 2 stand by (mask) function
Alarm 2 stand by (mask) function
This parameter is available only when OUT 2 is configured as
alarm 2 output (“O2.Fn” [C.E02] = “ALr.2”)
Upper display: Gr.6
Lower display: A2.St
Range: OFF = Stand-by function disabled
On
= Stand-by function enabled