R.E10 - Set point low limit

R.E10 - Set point low limit

R.E10 - Set point low limit

R.E10 - Set point low limit

R.E10 - Set point low limit
Upper display: Gr.5
Lower display: rL
Range: from input low range (depending on the "PV.SL" [C.D02]
setting) to rH [R.E11].
NOTES

NOTES

NOTES

NOTES

NOTES: Whenever "PV.SL" [C.D02] has been modified, the
following occurs:
1) rL will be realigned to the low limit; the realignement will be

carried out even if the set point is software protected.

2)If the set point values are out of the new limits, they automati-

cally assume the default value even if software protected.

R.E11 - Set point high limit.

R.E11 - Set point high limit.

R.E11 - Set point high limit.

R.E11 - Set point high limit.

R.E11 - Set point high limit.
Upper display: Gr.5
Lower display: rH
Range: from rL [R.E10] to input high range (depending on the
"PV.SL" [C.D02] setting).
NOTES

NOTES

NOTES

NOTES

NOTES: Whenever "PV.SL" [C.D02] has been modified, the
following occurs:
1) rH will be realigned to the low limit; the realignement will be

carried out even if the set point is software protected.

2) If the set point values are out of the new limits, they

automatically assume the default value even if software
protected.

R.E08 -

R.E08 -

R.E08 -

R.E08 -

R.E08 -Secondary control output max rate of rise

Secondary control output max rate of rise

Secondary control output max rate of rise

Secondary control output max rate of rise

Secondary control output max rate of rise

This parameter is available when one control output is configured
as secondary control output.
Upper display: Gr.5
Lower display: S.rñP
Ranges: from 0.1%/s to 25.0%/s.
Above this value the display shows “Inf” meaning that no limit is
imposed
NOTES

NOTES

NOTES

NOTES

NOTES:
1) This parameter will be active even if device is configured for

On/OFF control.

2) During the transfer from AUTO to MANUAL, if this action is

programmed as a not bumpless transfer, the “S.rñP” function
will be ignored and the output will step up to the value set by
“Añ.UL” [C.G04] parameter.

R.E09 - Secondary control output cycle time.

R.E09 - Secondary control output cycle time.

R.E09 - Secondary control output cycle time.

R.E09 - Secondary control output cycle time.

R.E09 - Secondary control output cycle time.
This parameter is available when a time proportional secondary
control output is configured.
Upper display: Gr.5
Lower display: SC.CY
Range: from 1 to 200 s