COF AND H2F ADJUSTMENT DIAGRAM

COF AND H2F ADJUSTMENT DIAGRAM

COF AND H2F ADJUSTMENT DIAGRAM

COF AND H2F ADJUSTMENT DIAGRAM

COF AND H2F ADJUSTMENT DIAGRAM
Others gas present in the atmosphere can
affect the carbon potential or the dew point
measurement.
By this chart it is possible to get the COF or
H2F factors able to correct the variation above
described.
If, for example, the instrument measures 0.4%
of carbon with a COF of 200 and the shim
stock analysis shows an actual carbon value of
0.35%,
draw a line between 0.4% and 200 and mark
the intersection on the pivot line.
Connect 0.35 of % Carbon with that
intersection and extend it till the COF scale (the
new COF value will be approximately 175).
Correct the COF [R.A05] parameter with the
new value.
NOTE:

NOTE:

NOTE:

NOTE:

NOTE: COF is equal to 10 • %CO and
H2F is 10 • %H2.

DEW

POINT

% CARBON

PIVOT

COF or H2F

Nominal H2F

in 40°F endo

Nominal COF

in 40°F endo