R.E03 - Main control output high limit
R.E03 - Main control output high limit
R.E03 - Main control output high limit
R.E03 - Main control output high limit
R.E03 - Main control output high limit
This parameter is available when one control output is configured
as main output.
Upper display: Gr.5
Lower display: ñ.OLH
Range: from ñ.OLL [R.E02] to 100.0 % of the output span.
R.E04 - Main control output max rate of rise
R.E04 - Main control output max rate of rise
R.E04 - Main control output max rate of rise
R.E04 - Main control output max rate of rise
R.E04 - Main control output max rate of rise
This parameter is available when one control output is configured
as main output.
Upper display: Gr.5
Lower display: ñ.rñP
Ranges: from 0.1%/s to 25.0%/s.
Above this value the display shows “Inf” meaning that no limit is
imposed.
NOTES
NOTES
NOTES
NOTES
NOTES:
1) This parameter will be active even if device is configured for
On/OFF control.
2) During the transfer from AUTO to MANUAL, if this action is
programmed as a not bumpless transfer, the “ñ.rñP” function
will be ignored and the output will step up to the value set by
“Añ.UL” [C.G04] parameter.
R.E05 - Main control output cycle time.
R.E05 - Main control output cycle time.
R.E05 - Main control output cycle time.
R.E05 - Main control output cycle time.
R.E05 - Main control output cycle time.
This parameter is available when time proportional main control
output is configured.
Upper display: Gr.5
Lower display: ñC.CY
Range: from 1 to 200 s
R.E06 - Secondary control output low limit
R.E06 - Secondary control output low limit
R.E06 - Secondary control output low limit
R.E06 - Secondary control output low limit
R.E06 - Secondary control output low limit
This parameter is available when one control output is configured
as secondary control output.
Upper display: Gr.5
Lower display: S.OLL
Range: From 0.0 % of the output span to S.OLH [R.E07].
R.E07 - Secondary control output high limit
R.E07 - Secondary control output high limit
R.E07 - Secondary control output high limit
R.E07 - Secondary control output high limit
R.E07 - Secondary control output high limit
This parameter is available when one control output is configured
as secondary control output.
Upper display: Gr.5
Lower display: S.OLH
Range: from S.OLL [R.E06] to 100.0 % of the output span.