1) Changing the controlled variable, the following parameters:

"CnF.6 - brG.L" [C.I03] and "CnF.6 - brG.H" [C.I04] (Bargraph
initial and full scale values);
"CnF.2 - O6.Lr" [C.E06] and "CnF.2 - O6.Hr" [C.E07] (Out 6
retransmission initial and full scale values);
"CnF.2 - O7.Lr" [C.E11] and "CnF.2 - O7.Hr" [C.E12] (Out 7
retransmission initial and full scale values);
"Gr.5 - rL" [R.E10] and "Gr.5 - rH" [R.E11]
(set point low and high limits); will be forced to the span limits
of the new selected variable.

2) SP, SP2, SP3, SP4 values and alarm thresholds, if out of the

limits for the new selected variable, will be forced to the low
limit value.

C.D03- Filter on probe sensor input (Main input)

C.D03- Filter on probe sensor input (Main input)

C.D03- Filter on probe sensor input (Main input)

C.D03- Filter on probe sensor input (Main input)

C.D03- Filter on probe sensor input (Main input)
Upper display: CnF.1
Lower display: Pb.FL
Ranges: from 0 (no filter) to 8 seconds.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
1) This is a first order digital filter applied on probe sensor input

value.

2) This filter can affect the control action, the alarms, the SMART

algorithm and the process variable retransmission.

C.D04 - Temperature input - TC type selection

C.D04 - Temperature input - TC type selection

C.D04 - Temperature input - TC type selection

C.D04 - Temperature input - TC type selection

C.D04 - Temperature input - TC type selection
Upper display: CnF.1
Lower display: tP.In
Ranges:

1 = TC K

From -100 to 1370 °C

2 = TC S

From

-50 to 1760 °C

3 = TC R

From

-50 to 1760 °C

4 = TC K

From -150 to 2500

°F

5 = TC S

From

-60 to 3200

°F

6 = TC R

From

-60 to 3200

°F

7= TC B

From 0 to 1820 °C

8= TC B

From 32 to 3300 °F

NOTE:

NOTE:

NOTE:

NOTE:

NOTE: When the controlled variable selected is dP, the span

limits of the following parameters:
"CnF.6 - brG.L" [C.I03] and "CnF.6 - brG.H" [C.I04]
(Bargraph initial and full scale values);
"CnF.2 - O6.Lr" [C.E06] and "CnF.2 - O6.Hr" [C.E07] (Out
6 retransmission initial and full scale values);
"CnF.2 - O7.Lr" [C.E11] and "CnF.2 - O7.Hr" [C.E12] (Out
7 retransmission initial and full scale values);
"Gr.5 - rL" [R.E10] and "Gr.5 - rH" [R.E11]
(set point low and high limits); will be forced to:
-100 to 100 °F if the temperature input has been

changed from a °C to a °F type;

-75 to 40 °C if the temperature input has been

changed from a °F to a °C type.