R.D04 - Derivative time
R.D04 - Derivative time
R.D04 - Derivative time
R.D04 - Derivative time
R.D04 - Derivative time
This parameter is available when at least one control output is
configured, “Cn.tP” [C.G02] is equal to “Pid” and "Pb" [R.D01] is
different from 0.
Upper display: Gr.4
Lower display: td
Range: From 00.00 to 10.00 mm.ss
NOTE
NOTE
NOTE
NOTE
NOTE:
When device is working with SMART algorithm and “Cn.tP”
[C.G02] is equal to “Pid”, the “td” value will be proportional to
the “ti” value with a ratio established during the "TUNE"
function.
R.D05 - Integral preload
R.D05 - Integral preload
R.D05 - Integral preload
R.D05 - Integral preload
R.D05 - Integral preload
This parameter is available when at least one control output is
configured and "Pb" [R.D01] is different from 0.
Upper display: Gr.4
Lower display: IP
Ranges:
- from 0.0 to 100.0 % of the output when device is configured
with only one control output.
- from -100.0 to 100.0 % of the output when device is
configured with two control outputs.
R.D06 - Relative secondary output gain
R.D06 - Relative secondary output gain
R.D06 - Relative secondary output gain
R.D06 - Relative secondary output gain
R.D06 - Relative secondary output gain
This parameter is available when two control outputs are
configured.
Upper display: Gr.4
Lower display: r.Gn
Range: from 0.20 to 2.00
R.D07 - Overlap/dead band between main and
R.D07 - Overlap/dead band between main and
R.D07 - Overlap/dead band between main and
R.D07 - Overlap/dead band between main and
R.D07 - Overlap/dead band between main and
secondary outputs
secondary outputs
secondary outputs
secondary outputs
secondary outputs
This parameter is available when two control outputs are
configured.
Upper display: Gr.4
Lower display: OLAP
Range: from -20 to 50
NOTE
NOTE
NOTE
NOTE
NOTE: A negative value means a dead band while a positive
value means an overlap.