Measurement Computing LogBook Series User Manual
Page 74

pg. 20, DBK Basics
967794
Daq Systems
DBK Power Requirement Worktable—Demand
DBK
Voltage Reference
Calculation
Options
+15 VDC
-15 VDC
+5 VDC
Quantity
× mW
= Sub Total
DBK1
0
0
0
0
DBK2
18 mA
18 mA
5 mA
565
DBK4
95 mA
80 mA
25 mA
2750
DBK5
2 mA
2 mA
15 mA
135
DBK7
14 mA
8 mA
18 mA
420
DBK8
15 mA
15 mA
<1 mA
455
DBK9
21 mA
16 mA
<1 mA
560
DBK10
0
0
0
0
DBK11A
0
0
0
0
DBK12
15 mA
15 mA
<1 mA
455
DBK13
15 mA
15 mA
<1 mA
455
DBK15
16 mA
16 mA
<1 mA
485
DBK16
37 mA
32 mA
<1 mA
1040
DBK17
30 mA
30 mA
<1 mA
905
DBK18
36 mA
36 mA
<1 mA
1085
DBK19
6 mA
7 mA
<1 mA
200
DBK20
0
0
<10 mA
50
DBK21
0
0
<10 mA
50
DBK23***
0
0
<2 mA
10
DBK24***
0
0
<2 mA
10
DBK25
0
0
<2 mA
10
DBK40
0
0
0
0
DBK41
0
0
0
0
DBK42
<1 mA
<1 mA
<1 mA
35
DBK43A***
<1 mA
<1 mA
<1 mA
35
DBK44
<1 mA
<1 mA
60 mA (Note 1)
330
DBK45
52 mA
52 mA
<1 mA
1565
DBK46
20 mA
20 mA
400 mA
2600
DBK48
<1 mA
<1 mA
<1 mA
35
DBK50***
<1 mA
<1 mA
<1 mA
35
DBK51***
<1 mA
<1 mA
<1 mA
35
DBK52
6 mA
7 mA
<1 mA
200
DBK53
15 mA
15 mA
<1 mA
455
DBK54
15 mA
15 mA
<1 mA
455
DBK55
30 mA
20 mA
40 mA
950
DBK60
0
0
0
0
Total Power Requirement in mW
Note 1: DBK44’s 60 mA value is based on 30 mA for each of two 5B modules. This value will be higher if using
5B module 5B38 (200 mA for each 5B38), or if using 5B39 (170 mA for each 5B39). Refer to the DBK44
document module for more information.
Note 2: DBK2 and DBK5 are not used with LogBook.
*** Three asterisks indicate that the DBK is a module with internal power supply; powered separately.
This table is continued.