The Atlas Fuel System
Preventive Maintenance
Page 66
MDE-4363F Atlas™ Fuel Systems Owner’s Manual · September 2011
Filter change and strainer
cleaning
New
Installations—
After 50,000
gallons (200,000
liters), or after
one month
Replace filters, and clean strainers regularly. An ASC must
perform these tasks.
ASC
After first filter
change—Every
300,000 gallons
(1.0 million liters),
every six months,
or when fuel
delivery rate
significantly
slows.
Inspect and lubricate
shear valves
Every six months
To inspect valve operation, perform the following tasks. If you
are not sure which device is the shear valve, have the ASC
inspect and lubricate this device for you.
Note: Shear valves are typically only used on dispensers. If you
have pumps, consult your installer to determine if they
were installed on your pump.
1
Trip the valve. For details, refer to
on
2
Authorize the hose at the console, if required.
3
Lift the operating handle.
4
Place the discharge nozzle in an approved container.
5
Squeeze the nozzle operating lever. If flow continues after
several seconds, the valve is defective.
6
Place a few drops of SAE10 oil on valve body shaft.
7
Open and close valve with a wrench several times.
8
Place valve back in service.
9
If repair is required, call an ASC.
• Owner—Inspect
• ASC only—Repair
and test
Components
Recommended
Frequency
Recommended Maintenance
Who Performs the
Inspection/Repair
WARNING
The pump/dispenser contains pressurized flammable fuel and lethal
voltages.
Servicing a Gasboy unit incorrectly could result in severe injury or death.
Do not attempt to service Gasboy pump/dispenser yourself and do not
allow untrained personnel to service Gasboy pumps/dispensers. Only
Gasboy-trained ASCs must service a Gasboy unit.
WARNING
The pump/dispenser contains pressurized flammable fuel and lethal
voltages.
Servicing a Gasboy unit incorrectly could result in severe injury or death.
Do not attempt to service Gasboy pump/dispenser yourself and do not
allow untrained personnel to service Gasboy pumps/dispensers. Only
Gasboy-trained ASCs must service a Gasboy unit.