beautypg.com

Refer to, Filter change and strainer cleaning, Warning – Gasboy Atlas Fuel Systems Owner Manual User Manual

Page 70

background image

The Atlas Fuel System

Preventive Maintenance

Page 66

MDE-4363F Atlas™ Fuel Systems Owner’s Manual · September 2011

Filter change and strainer
cleaning

New
Installations—
After 50,000
gallons (200,000
liters), or after
one month

Replace filters, and clean strainers regularly. An ASC must
perform these tasks.

ASC

After first filter
change—Every
300,000 gallons
(1.0 million liters),
every six months,
or when fuel
delivery rate
significantly
slows.

Inspect and lubricate
shear valves

Every six months

To inspect valve operation, perform the following tasks. If you
are not sure which device is the shear valve, have the ASC
inspect and lubricate this device for you.
Note: Shear valves are typically only used on dispensers. If you

have pumps, consult your installer to determine if they
were installed on your pump.

1

Trip the valve. For details, refer to

“Shear Valve”

on

page 40

.

2

Authorize the hose at the console, if required.

3

Lift the operating handle.

4

Place the discharge nozzle in an approved container.

5

Squeeze the nozzle operating lever. If flow continues after
several seconds, the valve is defective.

6

Place a few drops of SAE10 oil on valve body shaft.

7

Open and close valve with a wrench several times.

8

Place valve back in service.

9

If repair is required, call an ASC.

• Owner—Inspect
• ASC only—Repair

and test

Components

Recommended
Frequency

Recommended Maintenance

Who Performs the
Inspection/Repair

WARNING

The pump/dispenser contains pressurized flammable fuel and lethal
voltages.

Servicing a Gasboy unit incorrectly could result in severe injury or death.

Do not attempt to service Gasboy pump/dispenser yourself and do not
allow untrained personnel to service Gasboy pumps/dispensers. Only
Gasboy-trained ASCs must service a Gasboy unit.

WARNING

The pump/dispenser contains pressurized flammable fuel and lethal
voltages.

Servicing a Gasboy unit incorrectly could result in severe injury or death.

Do not attempt to service Gasboy pump/dispenser yourself and do not
allow untrained personnel to service Gasboy pumps/dispensers. Only
Gasboy-trained ASCs must service a Gasboy unit.