Power reset external adjustment, Warning, Caution – Gasboy Atlas Fuel Systems Owner Manual User Manual
Page 61

MDE-4363F Atlas™ Fuel Systems Owner’s Manual · September 2011
Page 57
Preventive Maintenance
The Atlas Fuel System
Component Inspections
To schedule component inspections, refer to
“Preventive Maintenance Table”
. The
station owner must only inspect for problems. For safety reasons, several tasks in the
“Preventive Maintenance Table”
including all repairs, must be performed only by
an ASC. To determine if an ASC must perform a task, refer to
“Who Performs the Inspection/Repair”
Power Reset External Adjustment
If the pump or remote dispenser unit fails to reset or shut-off properly, the reset motor must be
adjusted. To adjust, proceed as follows:
1
Loosen the lock nut on the adjusting screw and back screw out until it stops.
2
Move the reset lever to the ON position.
3
Turn adjustment screw in until reset motor starts.
4
Advance adjustment screw an additional 1/2 to 3/4 turn. Hold screw in this position and
tighten the lock nut.
WARNING
Leaking fuel can be ignited, causing a fire or explosion.
Fire, explosion, or electrical shock could result in severe injury or death if you continue to use
damaged pumps/dispensers.
If you find any leak or damage, stop using the pump/dispenser and contact your local ASC.
WARNING
The pump/dispenser contains pressurized flammable fuel and lethal voltages.
Servicing a Gasboy unit incorrectly could result in severe injury or death.
Do not attempt to service Gasboy pump/dispenser yourself and do not allow untrained personnel
to service Gasboy pumps/dispensers. Only Gasboy-trained ASCs must service a Gasboy unit.
Improperly installed or maintained equipment can create a hazard.
Improperly installed or maintained equipment could cause a fire, explosion, or electrical shock.
For any component not supplied by Gasboy (for example, hoses and nozzles), consult and
follow the installation and maintenance instructions provided by the manufacturer.
CAUTION