Warning – Gasboy Atlas Fuel Systems Owner Manual User Manual
Page 68

The Atlas Fuel System
Preventive Maintenance
Page 64
MDE-4363F Atlas™ Fuel Systems Owner’s Manual · September 2011
Breakaways
Once a week or
after drive-offs
1
Inspect breakaways for secure connection to hose and for
any leaks.
2
For units with hose retrievers, position the breakaway
coupling between the retriever connection to the hose and
the nozzle. The breakaway whip hose must be attached to
the nozzle.
3
Consult the breakaway manufacturer for any additional
required inspections.
4
If repair is required, call an ASC.
• Owner—Inspect
• ASC only—Repair
and test
Note: Not all breakaways are reusable after
separation. Follow manufacturer directions
for inspection and resetting for inspection
and resetting adjustable types.
Warning tags and
operating instructions
Once a week
Inspect for and replace all missing, damaged, or unreadable
warning tags or operating instructions.
• Owner—Inspect
• Owner or
ASC—Replace
Hose continuity
Once a month
Verify that the hose continuity (including breakaway whip hose)
complies with the hose manufacturer’s requirements.
• Owner—Inspect
• ASC only—Repair
Components
Recommended
Frequency
Recommended Maintenance
Who Performs the
Inspection/Repair
WARNING
Leaking fuel can be ignited, causing a fire or explosion.
Fire, explosion, or electrical shock could result in severe injury or death if
you continue to use damaged pumps/dispensers.
If you find any leak or damage, stop using the pump/dispenser and contact
your local ASC.
WARNING
The pump/dispenser contains pressurized flammable fuel and lethal
voltages.
Servicing a Gasboy unit incorrectly could result in severe injury or death.
Do not attempt to service Gasboy pump/dispenser yourself and do not
allow untrained personnel to service Gasboy pumps/dispensers. Only
Gasboy-trained ASCs must service a Gasboy unit.
WARNING
The pump/dispenser contains pressurized flammable fuel and lethal
voltages.
Servicing a Gasboy unit incorrectly could result in severe injury or death.
Do not attempt to service Gasboy pump/dispenser yourself and do not
allow untrained personnel to service Gasboy pumps/dispensers. Only
Gasboy-trained ASCs must service a Gasboy unit.