beautypg.com

Battery backup power supply for series 9800, Information for atc (series 9800 only) – Gasboy Atlas Fuel Systems Owner Manual User Manual

Page 31

background image

MDE-4363F Atlas™ Fuel Systems Owner’s Manual · September 2011

Page 27

Battery Backup Power Supply for Series 9800

The Atlas Fuel System

Battery Backup Power Supply for Series 9800

Figure 3-14: 9800 Series Power Supply

Series 9800 models can be equipped with an optional battery backup power supply. This
allows the last transaction data to be displayed for a minimum of 15 minutes. After the
batteries reach a certain low-voltage point, the power will automatically shut-off. If you have
to shut-off the battery power before the low-voltage point is reached, momentarily disconnect
and then re-connect the cable that plugs into P1 on the power supply.

The Atlas DEF 9862 cold and warm weather units do not use the battery on the power supply.

Information for ATC (Series 9800 Only)

By activating the magnet located at the opposite side of the totalizer, various items will appear
on the display.

On the ATC Status Display, the rightmost digit (2) indicates whether the temperature
compression is enabled or not. If enabled, it shows which product is being dispensed.

• 0=temperature compensation enabled
• 1=product is gasoline and compensation enabled
• 2=product is diesel and compensation enabled.

Note: Not used in the Atlas DEF 9862 units.

1.

Volume Display

Displays uncompensated volume

0023.43

2.

Probe Temperature

Display Displays probe temperature in Celsius only

023.2

3.

Flow Rate Display

Displays Flow Rate (in LPM only)

189.2

4.

Software Version Display

Displays software version number

1.30

5.

ATC Status Display

Displays ATC Status

842.2

P1 Connector