CPU Switch Settings (Series 9800 Only Including DEF 9862 Units)

The Atlas Fuel System

Pulser Output Rate Switches

When the Series 9800 is connected to external control equipment other than a Gasboy CFN,
Gasboy TopKAT top-mount or Gasboy TopKAT electronic (standalone), the pulser signals are
sent out via the 9800 Pump I/F PCB. The pulse rate required by the monitoring equipment can
be configured by setting the switches as shown in the following chart. The pulse rate
represents pulses per gallon (PPG for US Gallons and Imperial Gallons) or pulses per liter
(PPL, most international). For US Gallons or Imperial Gallons configurations, the pulse rate
can be up to 100 PPG for the 9850 and 500 PPG for all others models. For liters
configurations, the pulse rate can be up to 10 PPL for the 9840 and 9850, and 100 PPL for all
other models. For Imperial Gallons configurations, the pulse rate can be 100 PPG for the 9850
and 500 PPG for all other models. This switch must be sealed by a Weights and Measures
paper seal if the Series 9800 unit is used for the resale of product.

Leading zeroes are always suppressed in the hundreds and tens positions to the left of the
decimal point. When in standalone mode, positions to the right of the decimal point are
displayed based on the pulse rate selected as shown in the following table.

6

Open

Closed

Open

Closed

7

Closed

Open

Open

Closed

8

Open

Open

Open

Closed

9

Closed

Closed

Closed

Open

10

Open

Closed

Closed

Open

11

Closed

Open

Closed

Open

12

Open

Open

Closed

Open

13

Closed

Closed

Open

Open

14

Open

Closed

Open

Open

15

Closed

Open

Open

Open

16

Open

Open

Open

Open

Pulse Rate

SW2-1

SW2-2

SW2-3

1

Closed

Closed

Closed

10

Open

Closed

Closed

100

Closed

Open

Closed

250

Open

Open

Closed

500

Closed

Closed

Open

None

Closed

Open

Open

None

Open

Open

Open

Note: For the last two switch settings, no pulse will be sent to

the Fuel Management System.

Pulse Rate

9800/9840 Display Layout

9850 Display Layout

1:1

XXX.

XXXX.

10:1

XXX.X

XXXX.X

100:1

XXX.XX

XXXX.XX

250:1

XXX.XXX

XXXX.XX

500:1

XXX.XXX

XXXX.XX

Address

SW2-1

SW2-2

SW2-3

SW2-4