The Atlas Fuel System

Operating Sequence for Series 9800 Only

Page 48

MDE-4363F Atlas™ Fuel Systems Owner’s Manual · September 2011

After five seconds, a can size appears in the two Least Significant Digits (LSD, digits to the far
right) of the pump display (see

Figure 3-29

). The can size will appear for five seconds before

advancing to the next can size. The display will continue to scroll through can sizes until the
nozzle is removed and the pump handle is switched on.
Note: If the nozzle is not removed within 10 minutes of turning the switch to “Calibrate”

position, Error Code 574 appears (57 indicates time out, and 4 indicates calibration
mode error). Turn the Calibration switch to “Off” position (down), to clear the error.

Figure 3-29: Displaying the Can Size

2

After the required can size appears on the display, remove the nozzle and switch on the
pump handle.
This selects the can size for calibration.

Notes: 1) If the pump handle is switched on for an inappropriate can size and if the dispensing

has not started, switch off the pump handle. Scrolling will resume. If dispensing has
begun, switch off the pump handle, turn the Calibration switch to “Off” position,
and restart calibration from step

1

on

page 47

.

2) Must use an approved prover can for DEF calibrations.

3

Dispense fuel into the Prover Can exactly to the zero mark. The uncalibrated volume
appears.
Notes: 1) If the fuel/DEF is not dispensed within four minutes (approximately) of switching on

the pump handle (or within the time period set by the controller for pulser time out),
the Error Code 574 appears indicating that the pump handle must be switched off to
clear the error. Scrolling will resume after you replace the nozzle.

2) If fuel/DEF dispensing has started but stopped and the pump times out, the

Calibration switch must be turned to “Off” position. Else Error Code 993 appears
as shown in

Figure 3-30

on

page 49

(99 indicates that the product is not available,

and 3 indicates the product is not calibrated). The procedure must then be restarted
from step

1

on

page 47

.