Preventive Maintenance
The Atlas Fuel System
Meters, Valves
Once a month,
after drive-offs, or
as notified about
a potential leak
1
Whenever possible, Gasboy recommends removing power
to the unit before performing these inspections.
2
Block off the pump/dispenser to prevent customers from
operating the pump/dispenser during inspection.
3
Remove the lower panels slowly and carefully.
4
Inspect all hydraulic connections and seals, including the
following:
• Meters
• Valves
5
If wetness or dripping fuel is found, stop using the
pump/dispenser and make arrangements for repairing the
leak.
Note: Some staining of parts around seals is normal and
does not necessarily indicate a leak.
6
Monitor repaired components closely.
• Owner—Inspect
• ASC only—Repair
and test
Components
Recommended
Frequency
Recommended Maintenance
Who Performs the
Inspection/Repair
WARNING
Leaking fuel can be ignited, causing a fire or explosion.
Fire, explosion, or electrical shock could result in severe injury or death if
you continue to use damaged pumps/dispensers.
If you find any leak or damage, stop using the pump/dispenser and contact
your local ASC.
WARNING
WARNING
Self-contained pumps have a pinch point between the belts and the
pulleys.
Severe injury could occur if part of the body is pulled into the pinch point.
To prevent injury when inspecting self-contained units, do not place you
hands near the belts, pulleys, or motors. Turn off the power before
servicing the unit. Do not operate the unit with the door removed.
CAUT
WARNING
Gasoline or other fuels can damage the eyes.
Fuel sprayed into the eye can burn eye tissue.
To prevent potential injury, wear eye protection when performing these
inspections.
The pump/dispenser contains pressurized flammable fuel and lethal
voltages.
Servicing a Gasboy unit incorrectly could result in severe injury or death.
Do not attempt to service Gasboy pump/dispenser yourself and do not
allow untrained personnel to service Gasboy pumps/dispensers. Only
Gasboy-trained ASCs must service a Gasboy unit.