The Atlas Fuel System

CPU Switch Settings (Series 9800 Only Including DEF 9862 Units)

Page 26

MDE-4363F Atlas™ Fuel Systems Owner’s Manual · September 2011

Time-out Switch

When the Series 9800 is in standalone mode, it will turn off an active hose if it does not detect
pulses for four minutes, 15 seconds. This time-out feature can be disabled by setting switch
SW2-4 to OPEN.

SW2-5 and SW2-6: Unit of Measure Setting (New M06333KXXXX CPU Only)

These two switches select the Unit of Measurement: US Gallons, Imperial Gallons, and Liters.
For information, refer to the following table.

SW2-7: Electro-Mechanical Totalizer Enable (New M06333KXXXX CPU Only)

The K model pumps/dispensers have an option to use Electro-mechanical Totalizers. If these
are installed, then this switch must be set to CLOSED for proper operation of the totalizers.
This switch does not affect the operation of the electronic totalizer or the mechanical totalizer.

SW2-8: BDM Enable (New M06333KXXXX CPU Only)

This switch must always be set to OPEN for normal operation.

SW2-9: Software Download Enable (New M06333KXXXX CPU Only)

This switch must be OPEN for normal operation. When this switch is closed, it enables
loading new M06333KXXXX CPU software.

SW2-10 (New M06333KXXXX CPU Only)

This switch is not used.

Timeout

SW2-4

Enabled

Closed

Disabled

Open

Unit of Measure

SW2-5

SW2-6

US Gallons

Closed

Closed

Liters

Open

Closed

Imperial Gallons

Closed

Open

N/A

Open

Open

EM Totalizer

SW2-7

Enabled

Closed

Disabled

Open

Software Download Enable

SW2-9

Enabled

Closed

Disabled

Open