Series 9800 start-up error codes – Gasboy Atlas Fuel Systems Owner Manual User Manual
Page 54

The Atlas Fuel System
Series 9800 Start-up Error Codes
Page 50
MDE-4363F Atlas™ Fuel Systems Owner’s Manual · September 2011
Series 9800 Start-up Error Codes
The following Series 9800 start-up codes constantly appear at the far left on the power-up:
• 01-RAM Failure-RAM read/write tests failed
• 02-ROM Failure-bad ROM chip and checks failed
Start-up and Test Section for Series 9800 (except 9820)
Installation Completion Checklist
Review the following information to verify the proper installation of the Series 9800K
dispensing unit. If the installation does not meet the criteria listed, correct the problem before
the start-up is performed.
1
To avoid damage to the CPU PC board, verify that the RESET COMPLETE, FAST FLOW,
SUBM. STARTER DRIVE, and SLOW and FAST SATELLITE RETURN wires are not
shorted to the conduit or chassis.
2
The unit must be secured to the island properly.
3
All plumbing must be complete and tight. All liquid-carrying lines must be checked for leaks.
4
When DC pulser or RS-485 lines are used in the pump for connecting to Gasboy fuel
management systems, the AC and DC wires must not share any conduits, junction boxes, or
troughs.
5
All conduit work must be complete. All junction box covers must be secured. Conduits must
not be sealed until the wiring is verified through proper operation.
6
The unit must be grounded properly.
7
Before any testing begins, remove any water in the tank through a fill opening, using a suitable
pump.
Note: Do not use the Gasboy pump or remote dispenser and submersible pump to remove
water. Serious damage may occur.
8
A sufficient volume of fuel must be put in the tank to insure that the liquid level is above the
bottom of the suction pipe (suction pumps) or is high enough to allow the submersible pump to
operate efficiently (remote dispensers).
Start-up
After successfully verifying the installation against the completion checklist, the unit is ready
for start-up. To perform an orderly start-up of the Series 9800K, proceed as follows:
1
Verify if all switches on the CPU PCB are set properly for the various operating conditions.
2
Turn the circuit breakers on for the microprocessor and fluorescent lights. Verify if both lights
are lit.