beautypg.com

2 config: remote (remote control) – Comtech EF Data LBC-4000 User Manual

Page 64

background image

LBC-4000 L-Band Up/Down Converter System with Ethernet

Revision 2

Front Panel Operation

MN-LBC4000A

5–8

 

 

For the CONFIG: Conv‐A 

Æ

 ATTEN/SLOPE menu, the Ofst (Gain Offset) command is 

available only if redundancy is enabled. See Appendix B. LBC‐4000 REDUNDANCY 
OPERATION for further details on using this command in redundancy applications.
 

 
Press [ENT] when done. 

5.2.1.2 CONFIG: REMOTE (Remote Control)

Remote Control: LOCAL
SERIAL ETHERNET

 
Use the [][] arrow keys to select LOCALSERIAL or ETHERNET, and then press [ENT]

CONFIG: Remote Control

Æ LOCAL

When Remote Control Mode=LOCAL, remote control is disabled although remote 
monitoring is still possible. 

CONFIG: Remote Control

Æ SERIAL

Serial Mode = RS-232
Add=0001 Baud=9600 8-N-1

 
On the top line, to select the serial mode: Use the [][arrow keys to select select RS‐232 or 
RS‐485, and then press [ENT]
 
On the bottom line, to set the address: Use the [][arrow keys to navigate to the Address 
setting. Next, use the [][] arrow keys to select a digit to edit, and then use the [][] arrow 
keys to change its value. The valid range of addresses is from 0001 to 9999. Press [ENT] when 
done. 
 
On the bottom line, to set the baud rate: Use the [][arrow keys to navigate to the Baud 
setting.  Then,  use  the  [][arrow  keys  to  set  the  Baud  rate  of  the  remote  control  bus 
(connected locally to the M&C computer): 10024004800960019K2 (19200), or 38K4 (38400) 
baud are available. 
 
On the bottom line, to select the asynchronous character format: Use the [][] arrow keys 
to  navigate  to  the  format  setting.  Then,  use  the  [][]  arrow  keys  to  select  the  asynchronous 
character format as: 8N1 (8 data bits, no parity, 1 stop bit); 7O2 (7 data bits, odd parity, 2 stop 
bits); or 7E2 (7 data bits, even parity, 2 stop bits).  
 
Press [ENT] when done. 

CONFIG: Remote Control

Æ ETHERNET