Comtech EF Data SFC1800A User Manual
Page 95

SFC1800A Synthesized Frequency Upconverter
Appendix B
TM111 – Rev. 1.0
B-
3
DESCRIPTION
"Sets the Channel Gain in 0.1dB steps. -20.0 dB to 30.0 dB with an
implied decimal point. "
::= { radConverterNVStatus 2 }
radConverterCurrentChannel OBJECT-TYPE
SYNTAX
INTEGER (1..30)
MAX-ACCESS
read-write
STATUS
current
DESCRIPTION
"Channel number, 1 through 30. Selects the current channel of the unit.
Each channel allows entering of an independent set of parameters
(Frequency,
Gain, etc.). For example, Channel 1 Frequency might be set to 3.8GHz and
Channel 2 could be set to 4.0GHz. Any other parameters could be different
as well. The advantage is that a completely different setup can be arrived
at by merely changing the Channel number."
::= { radConverterNVStatus 3 }
radConverterCarrierControl OBJECT-TYPE
SYNTAX
INTEGER {
off(1),
on(2)
}
MAX-ACCESS
read-write
STATUS
current
DESCRIPTION
"Turns carrier off and on."
::= { radConverterNVStatus 4 }
radConverterMajorAlarmMask OBJECT-TYPE
SYNTAX
AlarmByteType
MAX-ACCESS
read-write
STATUS
current
DESCRIPTION
"Major Alarm mask:
Bit 0 = LO Fault
Bit 1 = Signal Fault
Bit 2-7 = Spares
0 = Mask, 1 = Allow"
::= { radConverterNVStatus 5 }
radConverterMinorAlarmMask OBJECT-TYPE
SYNTAX
AlarmByteType
MAX-ACCESS
read-write
STATUS
current
DESCRIPTION
"Minor Alarm mask:
Bit 0 = RF Dtect Fault
Bit 1 = IF Dtect Fault
Bit 2-7 = Spares
0 = Mask, 1 = Allow"
::= { radConverterNVStatus 6 }
-- --------------------------------------------------------------------------------------------------------------------
-- --------------------------------------------------------------------------------------------------------------------
-- Converter status information.
radConverterCarrierStatus OBJECT-TYPE
SYNTAX
INTEGER {
off(1),
on(2)
}
MAX-ACCESS
read-only
STATUS
current