Setup, 3 zone 2 connector – Artesyn ATCA-9405 Installation and Use (May 2014) User Manual

Page 45

background image

Setup

ATCA-9405 Installation and Use (6806800M71G)

45

2.3.3.3.3 Zone 2 Connector

The ATCA specifications define five identical connectors for the Zone 2 data transport. These
connectors are referred to as Free Board connectors and are assigned reference designators
P20 through P24 as per the ATCA specifications.

The ATCA-9405 is a node board and uses only two of the five connectors P20 and P23. P20 is
used to support clock synchronization interface and update channels and P23 is used to
support the base and fabric channels.

13

IPMC IMC PD0

IPMB Clock Port A

14

IPMC IMC PD1

IPMB Data Port A

15

IPMC ISC PC5

IPMB Clock Port B

16

IPMC ISC PC4

IPMB Data Port A

17-24

Not used

Not used

25

Shelf Ground

Shelf Ground

26

Logic Ground

Logic Ground

27

Power Building Block

Enable B

28

Power Building Block

Voltage Return A

29

Power Building Block

Voltage Return B

30

Power Building Block

Early -48V A

31

Power Building Block

Early -48V B

32

Power Building Block

Enable A

33

Power Building Block

-48V A

34

Power Building Block

-48V A

Table 2-11 Zone 1 Connector P10 Pin Assignment (continued)

Contact

Destination

Description