Chapter 4 Parameters|

Revision August 2008, 2ELE, V1.02

4-45

These parameters are used to determinate the frequency at stop:

When setting Pr.02.14 to 0: the initial frequency will be current frequency.

When setting Pr.02.14 to 1: the initial frequency will be 0.

When setting Pr.02.14 to 2: the initial frequency will be Pr.02.15.

02.16

Display the Master Freq Command Source

Settings

Read Only

Factory setting: ##

You can read the master frequency command source by this parameter.

Display Value

Bit

Function

1

Bit0=1 Master Freq Command Source by First Freq Source (Pr.02.00).

2

Bit1=1 Master Freq Command Source by Second Freq Source (Pr.02.09).

4

Bit2=1 Master Freq Command Source by Multi-input function

02.17

Display the Operation Command Source

Settings

Read Only

Factory setting: ##

You can read the operation source by this parameter.

Display Value

Bit

Function

1

Bit0=1 Operation Command Source by Digital Keypad

2

Bit1=1 Operation Command Source by RS485 communication

4

Bit2=1 Operation Command Source by External Terminal

8

Bit3=1 Operation Command Source by Multi-input function

02.18

User-defined Value 2 Setting

Unit: 1

Settings

0 to Pr.00.13

Factory Setting: 0