beautypg.com

Delta Electronics AC Motor Drive VFD-EL User Manual

Page 63

background image

Chapter 4 Parameters|

4-20

Revision August 2008, 2ELE, V1.02

Parameter

Explanation

Settings

Factory

Setting

Customer

10.20

Treatment of the
Erroneous PID
Feedback Level

0: Keep operating
1: Coast to stop
2: Ramp to stop
3: Ramp to stop and restart after time set in
Pr.10.21

0

10.21

Restart Delay Time
after Erroneous PID
Deviation Level

1 to 9999 sec

60

10.22

Set Point Deviation
Level

0 to 100%

0

10.23

Detection Time of
Set Point Deviation
Level

0 to 9999 sec

10

10.24

Offset Level of
Liquid Leakage

0 to 50%

0

10.25

Liquid Leakage
Change Detection

0 to 100% (0: disable)

0

10.26

Time Setting for
Liquid Leakage
Change

0.1 to 10.0 sec (0: disable)

0.5

10.27

|

10.33

Reserved