Chapter 4 Parameters|

Revision August 2008, 2ELE, V1.02

4-91

17H

17H

Data content

70H

Data content

70H

CRC CHK Low

86H

CRC CHK Low

86H

CRC CHK High

22H

CRC CHK High

22H

3.4 Check sum

ASCII mode:

LRC (Longitudinal Redundancy Check) is calculated by summing up, module 256, the values

of the bytes from ADR1 to last data character then calculating the hexadecimal

representation of the 2’s-complement negation of the sum.

For example, reading 1 word from address 0401H of the AC drive with address 01H.

STX

‘:’

‘0’

Address 1
Address 0

‘1’

‘0’

Function 1
Function 0

‘3’

‘0’

‘4’

‘0’

Starting data address

‘1’

‘0’

‘0’

‘0’

Number of data

‘1’

‘F’

LRC Check 1
LRC Check 0

‘6’

CR

END 1
END 0

LF

01H+03H+04H+01H+00H+01H=0AH, the 2’s-complement negation of 0AH is F6H.